"Since its founding in 1924, Mayekawa has focused on the development of freezing and cooling technology.Our technology began with cooling applications and we developed various components such as compressors, heat engineering devices and unmanned systems. Today we are moving into food processing, automation robotics and chemical plant equipment fields in both the domestic and international arenas"

 

 

 

 

 

 

 

 


Our Quality Policy
 

MYCOM, through its efforts to develop, accumulate and combine various technologies based on the above way of thinking is now able to offer a wide ranch of consistent services usually performed by individual consulting, engineering, manufacturing and plant engineering firms. Providing world-class technical service and expertise to customers of the Industrial Refrigeration Industry from the initial start-up to 20 years later. We are there for our customers providing support and personal one on one assistance on all aspects of service on MYCOM equipment and genuine Mycom parts, as well as other manufacturers. Our trained service technicians have many years of combined experience, and travel the globe to assist customers while providing the optimum level of service expected. This ability to provide reliable, comprehensive services to the customer based on extensive know-how aspects of industry is the cornerstone of MYCOM’s business.

The experts at MYCOM service and support the following:

  • Reciprocating Compressors
  • Screw Compressors
  • Engineered Design
  • Compressor Packages
  • Control Panels
  • Replacement Parts
  • On Site Training
  • Mycom Training Seminars
  • On-Site overhaul of Mycom Compressors
  • On-Site Start up Supervision and Assistance
 
  Recommended Maintenance      
Screw Compressors

Maintenance:
 
Oil Filters
Compressor
Oil Pump  
Compressor & Oil Pump Motors
Compressor & Oil Pump Filters
Control, Safety Interlocks & Set Points

after 500 Hrs   • Compressor Motor -Check Hot Alignment.
every 5,000 Hrs every 10,000 Hrs every 25,000 Hrs
  • Compressor Shaft Seal - Check and repair it if abnormal.
     
  • Compressor Unloader - Check and repair it if abnormal.
     
  • Suction Strainer - Dismantle and clean - first 200 hours.
     
  • Compressor Motor - Grease.
  • Compressor Bearings - Dismantle and check. Replace if necessary.
     
  • Oil Pump - Dismantle and check. Replace if necessary.
     
  • Compressor Oil - Submit oil sample for periodic analysis in a scheduled program (6-12 months). Please follow manufacturer's recommendations for oil type & brand.
     
  • Coalescer Element - Replace.
     
  • Oil Separator - Flush and Drain.
  • Compressor Thrust Bearings - Dismantle and check. Replace if necessary.
     
  • Compressor Main/Side Bearings - Replace.
     
  • Compressor O-Ring - Replace.
     
  • Compressor Gasket - Replace.
 
Reciprocating Compressors

Maintenance:
 
Oil Level - Check daily.
Compressor - Check head temperatures.
Oil Pressure - Check daily. 30-40psig net.
Compressor Motor & Belts - Check daily.
Compressor Cuno Filter - Turn handle 1/2 turn daily.
Control, Safety Interlocks & Set Points - Check weekly.

Six Month Interval Yearly or Beginning of Season
  • Compressor Shaft Seal - Check for oil or refrigerant leak.
     
  • Compressor Unloader - Check and repair it if abnormal.
     
  • Suction Strainer - Dismantle and clean.
     
  • Compressor Motor - Grease.
  • Compressor Bearings - Dismantle and check. Replace if necessary.
     
  • Oil Pump - Dismantle and check. Replace if necessary.
     
  • Oil Regulating Valve - Dismantle and clean.
     
  • Compressor Oil - Submit oil sample for periodic analysis in a scheduled program. Drain crankcase and refill as per MYCOM specs. Clean and replace internal oil strainer.
     
  • Suction and Discharge Valve Assemblies - Dismantle and repair if worn.
   
  Back to Top
   